V22.46

Scenario
Ryanfire SL Collar & Mastic to Ø160mm HDPE pipe through 150mm concrete floor
Fire Integrity
60 minutes
Insulation
60 minutes
Scenario
Ryanfire SL Collar & Mastic to Ø50mm HDPE pipe through 150mm concrete floor
Fire Integrity
180 minutes
Insulation
180 minutes
Scenario
Ryanfire SL Collar & Mastic to Ø65mm HDPE pipe through 150mm concrete floor
Fire Integrity
180 minutes
Insulation
180 minutes
Scenario
Ryanfire SL Collar & Mastic to Ø75mm HDPE pipe through 125mm concrete floor
Fire Integrity
120 minutes
Insulation
120 minutes
Scenario
Ryanfire SL Collar & Mastic to Ø100mm HDPE pipe through 125mm concrete floor
Fire Integrity
120 minutes
Insulation
120 minutes
V22.46
Brochure / Datasheet
Download